TAB Program Study Tools
Your Books
Enter values and press Calculate. Each result shows the formula with your numbers substituted in.
Slide to a frequency. Enter nameplate values to see how CFM, SP, and HP change under the fan laws.
NEMA limit: 1% max imbalance. Above 2% requires derating. Enter all three line-to-line voltages.
How hard is the motor working? Compare actual amps to nameplate FLA.
The theoretical no-load speed of a motor. Actual speed is slightly less due to slip.
F = CL × P0.65 — Pick a leakage class and test pressure, then enter duct area to find allowable leakage.
| Pressure Class | Inches w.g. | Pascals | Operating Pressure |
|---|---|---|---|
| 1/2" wg | 1/2" | 125 Pa | Up to 1/2" wg |
| 1" wg | 1" | 250 Pa | Over 1/2" to 1" wg |
| 2" wg | 2" | 500 Pa | Over 1" to 2" wg |
| 3" wg | 3" | 750 Pa | Over 2" to 3" wg |
| 4" wg | 4" | 1000 Pa | Over 3" to 4" wg |
| 6" wg | 6" | 1500 Pa | Over 4" to 6" wg |
| 10" wg | 10" | 2500 Pa | Over 6" to 10" wg |
| Duct Type | Default Leakage Class |
|---|---|
| Rectangular Duct | 16 |
| Round Duct | 8 |
| Oval Duct | 12 |
| Type | Best For | Notes |
|---|---|---|
| Mastic | Longitudinal seams, joints, large gaps | Flexible, long-lasting. Do not apply over dirt or oil. |
| Foil Tape | Joints, connections | Must be pressure class rated. Not all foil tape is approved. |
| Liquid Sealant | Penetrations, connections | Check manufacturer specs for temperature limits. |
| Duct Wrap + Mastic | Exposed ductwork requiring appearance | Used in schools, airports, public spaces. |
| Component | Purpose |
|---|---|
| Test Fan | Pressurizes the duct section to the specified test pressure |
| Orifice Tube | Measures airflow through the system; has orifice plate + two pressure taps |
| Two Manometers / Magnehelics | One measures SP in duct; one measures ΔP across orifice plate |
| Calibration Chart | Converts ΔP reading to actual CFM leakage rate for the specific orifice tube |
| Tubing | Connects pressure taps to manometers |
| Class | Name | Requirement |
|---|---|---|
| A | Most Restrictive | Seal ALL transverse joints, longitudinal seams, and penetrations |
| B | Moderate | Seal ALL transverse joints. Seams unsealed unless specified. |
| C | Least Restrictive | No sealing required unless specified. Low-pressure systems. |
| Duct Type | Default CL |
|---|---|
| Rectangular | 16 |
| Round | 8 |
| Oval | 12 |
| Class | In. w.g. | Operating Pressure Range |
|---|---|---|
| 1/2" | 0.5 | Up to 1/2" wg |
| 1" | 1.0 | Over 1/2" to 1" wg |
| 2" | 2.0 | Over 1" to 2" wg |
| 3" | 3.0 | Over 2" to 3" wg |
| 4" | 4.0 | Over 3" to 4" wg |
| 6" | 6.0 | Over 4" to 6" wg |
| 10" | 10.0 | Over 6" to 10" wg |
| Type | Best For | Notes |
|---|---|---|
| Mastic | Seams, joints, gaps | Flexible. Clean surface — no dirt or oil. |
| Foil Tape | Joints, connections | Must be pressure class rated. |
| Liquid Sealant | Penetrations | Check temperature limits. |
No notes saved yet. Open a lesson unit and write notes below each beat.
Lessons